Indirect connection of energy SL7000 meters with and without Voltage transformer

Indirection connection without Voltage Transformers

  1. Introduction
  2. The indirect connection of SL7000 energy meters without measurement voltage transformers is the type of connection in which connections to the voltage circuits of the meter are done directly. The energy meter and current carrying conductor or busbar of the system both share the same voltage magnetude. This therefore means that any voltage perturbation on the current carrying conductors is channelled directly to the energy meter. This method of connection exposes the energy meter more to external influences like voltage surges and over currents. A line diagram of this method of connection is shown below in figure 01. Indirect connection without VTs

    Figure 01: Indirect connection of SL7000 energy meter without VT

From figure 01 above, we can retrieve the following information:

NB: This configuration method is suitable for connecting energy meters in a system with lower voltage variations. For example, isolated systems.

Indirection connection with Voltage Transformers

  1. Introduction
  2. The indirect connection of SL7000 energy meters with VTs is the one in which connections to the energy meter's voltage circuits are carried out using VTs. Voltage perturbation on the busbar will not affect the energy meter as it is been scaled down by the VTs. The voltage transformers as a result provide protections against surges and overcurrent. A line diagram of this method of connection is shown in figure 02 below. Indirect connection with VTs

    Figure 02: Indirect connection of SL7000 energy meter with VT

From figure 02 above, we can retrieve the following information:

NB: This configuration method is the most suitable method for connecting energy meters as it provides protection against overvoltages which are in most cases the main cause of meter failures.
Eventhough it is the most suitable method for connecting energy meters, it can also cause meter failures and false readings if the VTs used are poorly selected. For example using protection voltage transformers for measurement is relatively a bad idea as these transformers do not get saturated quickly under fault conditions as compared to measurement VTs. In addition, they also produce distorted ouput under fault conditions which will enable meters to produce false readings.
Thus, proper care should be taken when selecting voltage transformers for measurement to ensure the chosen VTs are main for measurements. To better comprehend this, you can check out at: criteria for selecting VTs for measurements.

Conclusion
Studies have proven that the constant voltage flow of the electrical system can be disrupted by sudden, brief power demands. Hundreds of these small power surges occur every day, usually when devices with motors turn on or off, diverting electricity between them. Additionally, it is also stated that it is possible for a system to operate for hundreds of hours without sufficient current increase. In addition, It is relatively difficult to protect energy meters against overvoltages using a protective device (e.g surge protector), because each protective device has a threshold value that must be exceeded before it can react. A digital meter has very fragile electronic components like AD converters, micro controller, capacitors, resistors, MCT and cannot wait for a protective device to reach its threshold level. Analog meters will operate normally during power surges because they do not contain semiconductor components. Therefore, a better way to improve the metering system is by applying the indirect connection with voltage transformers method.